Toshiba inverter-Tosvert VF-FS1 wiring device

Home > Industrial Control > Toshiba inverter > VF-FS1 >

Toshiba inverter-Tosvert VF-FS1 wiring device 

Typeform Input
phase
[PH]
Volatge
class
[V]
Capacity
[kW]
MCCB MC
Without
DCL
With
DCL
Without
DCL(ACL)
With
DCL(ACL)
Rated
current
[A]
Typeform Rated
current
[A]
Typeform Typeform Typeform
VFFS1-2004PM 3 200 0.4 3 NJ30E     CA13  
VFFS1-2007PM 3 200 0.75 5 NJ30E     CA13  
VFFS1-2015PM 3 200 1.5 10 NJ30E     CA13  
VFFS1-2022PM 3 200 2.2 15 NJ30E     CA13  
VFFS1-2037PM 3 200 3.7 30 NJ30E     CA13  
VFFS1-2055PM 3 200 5.5 40 NJ50EB     CA20  
VFFS1-2075PM 3 200 7.5 50 NJ50EB     CA25  
VFFS1-2110PM 3 200 11 75 NJ100FB     CA35  
VFFS1-2150PM 3 200 15 100 NJ100FB     CA50  
VFFS1-2185PM 3 200 18.5 100 NJ225FB     CA50  
VFFS1-2220PM 3 200 22 125 NJ225FB     CA65  
VFFS1-2300PM 3 200 30 175 NJ225FB     CA80  
VFFS1-4004PL 3 400 0.4 3 NJ30E     CA13  
VFFS1-4007PL 3 400 0.75 3 NJ30E     CA13  
VFFS1-4015PL 3 400 1.5 5 NJ30E     CA13  
VFFS1-4022PL 3 400 2.2 10 NJ30E     CA13  
VFFS1-4037PL 3 400 3.7 15 NJ30E     CA13  
VFFS1-4055PL 3 400 5.5 20 NJ30E     CA13  
VFFS1-4075PL 3 400 7.5 30 NJ30E     CA20  
VFFS1-4110PL 3 400 11 40 NJ50EB     CA20  
VFFS1-4150PL 3 400 15 50 NJ50EB     CA25  
VFFS1-4185PL 3 400 18.5 60 NJ100FB     CA35  
VFFS1-4220PL 3 400 22 75 NJ100FB     CA50  
VFFS1-4300PL 3 400 30 100 NJ100FB     CA50  


[Wiring Devices] [Cable size/Screw size]
Typeform Input
phase
[PH]
Volatge
class
[V]
Capacity
[kW]
Cable size Screw size
Main
[mm2]
DCL
[mm2]
PBR
[mm2]
G/E
[mm2]
Main Control G/E
VFFS1-2004PM 3 200 0.4 2 - - 2 M4 M3 M4, M5(FIN)
VFFS1-2007PM 3 200 0.75 2 - - 2 M4 M3 M4, M5(FIN)
VFFS1-2015PM 3 200 1.5 2 - - 2 M4 M3 M4, M5(FIN)
VFFS1-2022PM 3 200 2.2 2 - - 2 M4 M3 M4, M5(FIN)
VFFS1-2037PM 3 200 3.7 2 - - 2 M4 M3 M4, M5(FIN)
VFFS1-2055PM 3 200 5.5 3.5 - - 3.5 M5 M3 M5, M5(FIN)
VFFS1-2075PM 3 200 7.5 5.5 - - 3.5 M5 M3 M5, M5(FIN)
VFFS1-2110PM 3 200 11 14 - - 5.5 M6 M3 M6, M5(FIN)
VFFS1-2150PM 3 200 15 14 - - 5.5 M6 M3 M6, M5(FIN)
VFFS1-2185PM 3 200 18.5 22 - - 8 M6 M3 M6, M5(FIN)
VFFS1-2220PM 3 200 22 38 - - 8 M8 M3 M8, M5(FIN)
VFFS1-2300PM 3 200 30 38 - - 14 M8 M3 M8, M5(FIN)
VFFS1-4004PL 3 400 0.4 2 - - 2 M4 M3 M4, M5(FIN)
VFFS1-4007PL 3 400 0.75 2 - - 2 M4 M3 M4, M5(FIN)
VFFS1-4015PL 3 400 1.5 2 - - 2 M4 M3 M4, M5(FIN)
VFFS1-4022PL 3 400 2.2 2 - - 2 M4 M3 M4, M5(FIN)
VFFS1-4037PL 3 400 3.7 2 - - 2 M4 M3 M4, M5(FIN)
VFFS1-4055PL 3 400 5.5 2 - - 2 M4 M3 M4, M5(FIN)
VFFS1-4075PL 3 400 7.5 2 - - 2 M5 M3 M5, M5(FIN)
VFFS1-4110PL 3 400 11 3.5 - - 3.5 M5 M3 M5, M5(FIN)
VFFS1-4150PL 3 400 15 5.5 - - 3.5 M6 M3 M6, M5(FIN)
VFFS1-4185PL 3 400 18.5 5.5 - - 5.5 M6 M3 M6, M5(FIN)
VFFS1-4220PL 3 400 22 8 - - 5.5 M8 M3 M8, M5(FIN)
VFFS1-4300PL 3 400 30 14 - - 5.5 M8 M3 M8, M5(FIN)

NOTICE:
*1: [x2],[x3],[x4] means parallel number of cable.
*2: The wire size is for 600V HIV wire (75 degreeC).
    Ambient termperature is less than 50 degreeC and Wire length is less than 30m.
*3: The wire for control signal is shielded wire with 0.75mm2 or more.
*4: Please use large size wire for G/E compared than above table.
.

Read more