Toshiba inverter-Tosvert VF-MB1 standard spec
Home > Industrial Control > Toshiba inverter > VF-MB1 >
Toshiba inverter-Tosvert VF-MB1 standard spec
Standard specificaitons -
1-phase 240V
Item | Specification | |||||
Input voltage class | 1-phase 240V class | |||||
Applicable motor (kW) | 0.2 | 0.4 | 0.75 | 1.5 | 2.2 | |
Rating | Type | VFMB1S- | ||||
Form | 2002PL | 2004PL | 2007PL | 2015PL | 2022PL | |
Capacity (kVA) Note 1) | 0.6 | 1.3 | 1.8 | 3.0 | 4.2 | |
Rated output current (A) Note 2) |
1.5 (1.5) | 3.3 (3.3) | 4.8 (4.8) | 8.0 (8.0) | 11.0 (11.0) | |
Output voltage Note 3) | 3-phase 200V to 240V | |||||
Overload current rating Note 2) | 150%-60 seconds, 200%-0.5 second (120%-60 seconds, 165%-0.5 second) | |||||
Power supply | Voltage-frequency | 1-phase 200V to 240V - 50/60Hz | ||||
Allowable fluctuation | Voltage 170 to 264V Note 4), frequency ±5% | |||||
Required Power supply capacity (kVA) Note 5) |
0.8 | 1.4 | 2.3 | 4.0 | 5.4 | |
Protective method (IEC60529) | IP20 | |||||
Cooling method | Forced air-cooled | |||||
Color | RAL7016 | |||||
Built-in fi lter | EMC filter |
3-phase 500V
Item | Specification | |||||||||
Input voltage class | 3-phase 500V class | |||||||||
Applicable motor (kW) | 0.4 | 0.75 | 1.5 | 2.2 | 4.0 | 5.5 | 7.5 | 11 | 15 | |
Rating | Type | VFMB1- | ||||||||
Form | 4004PL | 4007PL | 4015PL | 4022PL | 4037PL | 4055PL | 4075PL | 4110PL | 4150PL | |
Capacity (kVA) Note 1) | 1.1 | 1.8 | 3.1 | 4.2 | 7.2 | 11 | 13 | 21 | 25 | |
Rated output current (A) Note 2) |
1.5 (1.5) |
2.3 (2.3) |
4.1 (4.1) |
5.5 (5.5) |
9.5 (9.5) |
14.3 (17.0) |
17.0 (23.0) |
27.7 (33.0) |
33.0 (40.0) |
|
Output voltage Note 3) | 3-phase 380V to 500V | |||||||||
Overload current rating Note 2) | 150%-60 seconds, 200%-0.5 second (120%-60 seconds, 165%-0.5 second) | |||||||||
Power supply | Voltage-frequency | 3-phase 380V to 500V - 50/60Hz | ||||||||
Allowable fluctuation | Voltage 323 to 550V Note 4), frequency ±5% | |||||||||
Required Power supply capacity (kVA) Note 5) |
1.6 | 2.6 | 4.7 | 6.3 | 10.1 | 15.2 | 19.6 | 26.9 | 34.9 | |
Protective method (IEC60529) | IP20 | |||||||||
Cooling method | Forced air-cooled | |||||||||
Color | RAL7016 | |||||||||
Built-in filter | EMC fi lter |
Note 1. Capacity is calculated at 220V for the 240V models, at 440V for the 500V models.
Note 2. It is a value when the inverter overload characteristic selection (parameter aul) is the constant torque characteristic.
Value in ( ) for the variable torque characteristic.
The output current must be reduced according to the PWM carrier frequency, ambient temperature and supply voltage.
Note 3. Maximum output voltage is the same as the input voltage.
Note 4. At 180V-264V for the 240V models, at 342V-550V for the 500V models when the inverter is used continuously (load of 100%).
Note 5. Required power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).