Toshiba inverter-Tosvert VF-MB1 wiring device
Home > Industrial Control > Toshiba inverter > VF-MB1 >
Toshiba inverter-Tosvert VF-MB1 wiring device
Typeform |
Input phase [PH] |
Volatge class [V] |
Capacity [kW] |
MCCB | MC | ||||
Without DCL |
With DCL |
Without DCL(ACL) |
With DCL(ACL) |
||||||
Rated current [A] |
Typeform |
Rated current [A] |
Typeform | Typeform | Typeform | ||||
VFMB1S-2002PL | 1 | 240 | 0.2 | 5 | NJ30E | 5 | NJ30E | CA13 | CA13 |
VFMB1S-2004PL | 1 | 240 | 0.4 | 10 | NJ30E | 10 | NJ30E | CA13 | CA13 |
VFMB1S-2007PL | 1 | 240 | 0.75 | 15 | NJ30E | 10 | NJ30E | CA13 | CA13 |
VFMB1S-2015PL | 1 | 240 | 1.5 | 30 | NJ30E | 20 | NJ30E | CA20 | CA13 |
VFMB1S-2022PL | 1 | 240 | 2.2 | 30 | NJ30E | 30 | NJ30E | CA20 | CA20 |
VFMB1-4004PL | 3 | 500 | 0.4 | 5 | NJ30E | 5 | NJ30E | CA13 | CA13 |
VFMB1-4007PL | 3 | 500 | 0.75 | 5 | NJ30E | 5 | NJ30E | CA13 | CA13 |
VFMB1-4015PL | 3 | 500 | 1.5 | 10 | NJ30E | 10 | NJ30E | CA13 | CA13 |
VFMB1-4022PL | 3 | 500 | 2.2 | 15 | NJ30E | 10 | NJ30E | CA13 | CA13 |
VFMB1-4037PL | 3 | 500 | 4.0 | 20 | NJ30E | 15 | NJ30E | CA13 | CA13 |
VFMB1-4055PL | 3 | 500 | 5.5 | 30 | NJ30E | 20 | NJ30E | CA20 | CA13 |
VFMB1-4075PL | 3 | 500 | 7.5 | 30 | NJ30E | 30 | NJ30E | CA20 | CA20 |
VFMB1-4110PL | 3 | 500 | 11 | 50 | NJ50EB | 40 | NJ50EB | CA25 | CA20 |
VFMB1-4150PL | 3 | 500 | 15 | 60 | NJ100FB | 50 | NJ50EB | CA35 | CA25 |
[Wiring Devices] [Cable size/Screw size]
Typeform |
Input phase [PH] |
Volatge class [V] |
Capacity [kW] |
Cable size | Screw size | |||||
Main [mm2] |
DCL [mm2] |
PBR [mm2] |
G/E [mm2] |
Main | Control | G/E | ||||
VFMB1S-2002PL | 1 | 240 | 0.2 | 1.5 | - | 1.5 | 2.5 | M3 | M3 | M4, M5 |
VFMB1S-2004PL | 1 | 240 | 0.4 | 1.5 | - | 1.5 | 2.5 | M3 | M3 | M4, M5 |
VFMB1S-2007PL | 1 | 240 | 0.75 | 1.5 | - | 1.5 | 2.5 | M3 | M3 | M4, M5 |
VFMB1S-2015PL | 1 | 240 | 1.5 | 2.5 | - | 1.5 | 2.5 | M3 | M3 | M4, M5 |
VFMB1S-2022PL | 1 | 240 | 2.2 | 4.0 | - | 1.5 | 3.5 | M3 | M3 | M4, M5 |
VFMB1-4004PL | 3 | 500 | 0.4 | 1.5 | - | 1.5 | 2.0 | M3 | M3 | M4, M5 |
VFMB1-4007PL | 3 | 500 | 0.75 | 1.5 | - | 1.5 | 2.0 | M3 | M3 | M4, M5 |
VFMB1-4015PL | 3 | 500 | 1.5 | 1.5 | - | 1.5 | 2.0 | M3 | M3 | M4, M5 |
VFMB1-4022PL | 3 | 500 | 2.2 | 1.5 | - | 1.5 | 2.0 | M3 | M3 | M4, M5 |
VFMB1-4037PL | 3 | 500 | 4.0 | 2.5 | - | 1.5 | 2.0 | M3 | M3 | M4, M5 |
VFMB1-4055PL | 3 | 500 | 5.5 | 4.0 | - | 1.5 | 3.5 | M4 | M3 | M5 |
VFMB1-4075PL | 3 | 500 | 7.5 | 6.0 | - | 2.5 | 3.5 | M4 | M3 | M5 |
VFMB1-4110PL | 3 | 500 | 11 | 10.0 | - | 4.0 | 5.5 | M4 | M3 | M5 |
VFMB1-4150PL | 3 | 500 | 15 | 16.0 | - | 6.0 | 5.5 | M4 | M3 | M5 |
NOTICE:
*1: [x2],[x3],[x4] means parallel number of cable.
*2: The wire size is for 600V HIV wire (75 degreeC).
Ambient termperature is less than 50 degreeC and Wire length is less than 30m.
*3: The wire for control signal is shielded wire with 0.75mm2 or more.
*4: Please use large size wire for G/E compared than above table. .