Toshiba inverter-Tosvert VF-PS1 standard spec
Home > Industrial Control > Toshiba inverter > VF-PS1 >
Toshiba inverter-Tosvert VF-PS1 standard spec
- Standard specificaitons -
200V class
Item | Specification | ||||||||||||||
Applicable motor (kW) | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | |
Rating | Type | VFPS1- | |||||||||||||
Form | 2004PL | 2007PL | 2015PL | 2022PL | 2037PL | 2055PL | 2075PL | 2110PM | 2150PM | 2185PM | 2220PM | 2300PM | 2370PM | 2450PM | |
Output Capacity (kVA) Note 1) | 1.1 | 1.8 | 3.0 | 4.2 | 6.7 | 10.0 | 13 | 21 | 25 | 29 | 34 | 46 | 55 | 67 | |
Output Current (A) Note 2) |
3.0 (3.0) |
4.8 (4.5) |
8.0 (8.0) |
11 (10.5) |
17.5 (16.6) |
27.5 (25.0) |
33 (33) |
54 (49) |
66 (64) |
75 (66) |
88 (75) |
120 (88) |
144 (120) |
176 (140) |
|
Output Voltage | 3-phase, 200 to 240 V (The maximum output voltage is the same as the input voltage.) | ||||||||||||||
Overload current rating | 120% - 1 minute 135% - 2 seconds | ||||||||||||||
Electric braking | Dynamic Braking Circuit | Built-in | |||||||||||||
Dynamic Breaking Resistor | External options | ||||||||||||||
Power supply | Voltage-frequency | 3-phase, 200 to 240 V . 50/60 Hz | |||||||||||||
Allowable fluctuation | Voltage +10% - 15% Note 3) Frequency +/-5% | ||||||||||||||
Protective method | IP20 enclosed type (JEM1030) | IP00 enclosed type (JEM1030) Note 4) | |||||||||||||
Cooling method | Forced air-cooled | ||||||||||||||
Cooling fan noise (dBA) | 43 | 43 | 43 | 55 | 55 | 56 | 58 | 60 | 60 | 60 | 60 | 64 | 64 | 64 | |
Color | RAL7016 | ||||||||||||||
Built-in Filter | EMC noise filter Note 5) | Basic noise filter Note 6) | |||||||||||||
DC Reactor | External option | Built-in |
400V class
Item | Specification | |||||||||||||||
Applicable motor (kW) | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | 75 | |
Rating | Type | VFPS1- | ||||||||||||||
Form | 4007PL | 4015PL | 4022PL | 4037PL | 4055PL | 4075PL | 4110PL | 4150PL | 4185PL | 4220PL | 4300PL | 4370PL | 4450PL | 4550PL | 4750PL | |
Output Capacity (kVA) Note 1) | 1.8 | 3.1 | 4.4 | 8.0 | 11 | 13 | 21 | 25 | 31 | 37 | 50 | 60 | 72 | 88 | 122 | |
Output Current (A) Note 2) |
2.3 (2.3) |
4.1 (4.0) |
5.8 (5.3) |
10.5 (8.6) |
14.3 (13) |
17.6 (17) |
27.7 (25) |
33 (32) |
41 (37) |
48 (38) |
66 (53) |
79 (60) |
94 (75) |
116 (93) |
160 (120) |
|
Output Voltage | 3-phase, 380 to 480 V (The maximum output voltage is the same as the input voltage.) | |||||||||||||||
Overload current rating | 120% - 1 minute 135% - 2 seconds | |||||||||||||||
Electric braking | Dynamic Braking Circuit | Built-in | ||||||||||||||
Dynamic Breaking Resistor | External options | |||||||||||||||
Power supply | Voltage-frequency | 3-phase, 380 to 480 V . 50/60 Hz | ||||||||||||||
Allowable fluctuation | Voltage +10% - 15% Note 3) Frequency +/-5% | |||||||||||||||
Protective method | IP20 enclosed type (JEM1030) | IP00 enclosed type (JEM1030) Note 4) | ||||||||||||||
Cooling method | Forced air-cooled | |||||||||||||||
Cooling fan noise (dBA) | 43 | 43 | 43 | 55 | 56 | 56 | 58 | 60 | 60 | 60 | 64 | 64 | 64 | 64 | 64 | |
Color | RAL7016 | |||||||||||||||
Built-in Filter | EMC noise filter Note 5) | |||||||||||||||
DC Reactor | External option | Built-in |
Note 1) Capacity is calculated at 220V for the 200V models and at 440V for the 400V models.
Note 2) Rated output current when the PWM carrier frequency (parameter ) is 4kHz or less. The values in parentheses refer to rated output currents when set to 12kHz.
Note 3) +/-10% when the inverter is used continuously (load of 100%)
Note 4) Inverters, 18.5kW or greater, do not have wiring port covers. They have large openings, but there is no space to bend the external cables inside the unit. If they are fitted external to the cabinet, please use an optional wiring port cover.
Note 5) Complies with the Europian EMC Directive IEC/EN61800-3, 1st environment, category C2 or IEC/EN61800-3, 2nd environment, category C3
Note 6) Not complies with the European EMC Directive Core and capacities with external filter (optional) : Complies with the Europien EMC Directive.
Standard specifications (200 V class -55 to 75 kW)
Item | Specification | |||
Applicable motor (kW) | 55 | 75 | 90 | |
Rating | Type | VFPS1- | ||
Form | 2550P | 2750P | 2900P | |
Output Capacity (kVA) Note 1) | 84 | 109 | 137 | |
Output Current (A) Note 2) | 221 | 285 | 359 | |
Output Voltage | 3-phase, 200 to 240 V (The maximum output voltage is the same as the input voltage.) | |||
Overload Current Rating | 120% - 1 minute 135% - 2 seconds | |||
Electric braking | Dynamic Braking Circuit | Built-in | ||
Dynamic Breaking Resistor | External options | |||
Power supply | Voltage/frequency | 3-phase, 200 to 240 V . 50/60 Hz | ||
Allowable Fluctuation | Voltage +10% . 15% Note 3) Frequency +/-5% | |||
Protective method | IP00 open type (JEM1030) Note 4) | |||
Cooling method | Forced air cooling | |||
Cooling fan noise (dBA) | 61 | 61 | 70 | |
Color | RAL7016 | |||
Built-in Filter | External filter (optional) | |||
DC Reactor | Attached DC reactor Note 5) |
Standard specifications (400 V class -90 to 630 kW model)
Item | Specification | |||||||||||
Applicable motor (kW) | 90 | 110 | 132 | 160 | 220 | 250 | 280 | 315 | 400 | 500 | 630 | |
Rating | Type | VFPS1- | ||||||||||
Form | 4900PC | 4110KPC | 4132KPC | 4160KPC | 4220KPC | 4250KPC | 4280KPC | 4315KPC | 4400KPC | 4500KPC | 4630KPC | |
Output Capacity (kVA) Note 1) | 136 | 164 | 197 | 239 | 325 | 367 | 419 | 469 | 578 | 717 | 905 | |
Output Current (A) Note 2) | 179 | 215 | 259 | 314 | 427 | 481 | 550 | 616 | 759 | 941 | 1188 | |
Output Voltage | 3-phase, 380 to 480 V (The maximum output voltage is the same as the input voltage.) | |||||||||||
Overload Current Rating | 120% - 1 minute, 135% - 2 seconds | |||||||||||
Electric braking | Dynamic Braking Circuit | Built-in | External options | |||||||||
Dynamic Breaking Resistor | External options | |||||||||||
Power supply | Voltage/frequency | Note 6) |
3-phase, 380 to 440 V . 50 Hz 3-phase, 380 to 480 V . 60 Hz |
|||||||||
Allowable Fluctuation | Voltage +10% . 15% Note 3) Frequency +/-5% | |||||||||||
Protective method | IP00 open type (JEM1030) Note 4) | |||||||||||
Cooling method | Forced air cooling | |||||||||||
Cooling fan noise (dBA) | 61 | 61 | 72 | 73 | 73 | 76 | 76 | 76 | 76 | 76 | 78 | |
Color | RAL7016 | |||||||||||
Built-in Filter | EMC noise filter Note 7) | |||||||||||
DC Reactor | Attached DC reactor Note 5) |
Note 1) Capacity is calculated at 220V for the 200V models and at 440V for the 400V models.
Note 2) Indicates the value when the PWM carrier frequency (parameter ) is 2.5 kHz or less. When low noise (PWM carrier frequency 8 kHz) is required at 18.5 kW or more, use an inverter of capacity one rank higher than the motor capacity.
Note 3) +/-10% when the inverter is used continuously (load of 100%)
Note 4) Inverters, 18.5kW or greater, do not have wiring port covers. They have large openings, but there is no space to bend the external cables inside the unit. If they are fitted external to the cabinet, please use an optional wiring port cover.
Note 5) For 200V-55kW, 400V-90kW or larger model, be sure to install DC reactor. However, this is unnecessary for DC input specifications.
Note 6) Three-phase 380~480V-50/60Hz
Note 7) Complies with the European EMC Directive
IEC/EN61800-3, 2nd environment, category C3
Totally enclosed box type
Item | Specification | |||||||||||||||||
Voltage class | 400V class | |||||||||||||||||
Applicable motor (kW) | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | 75 | 90 | ||
Applicable motor (HP) | 1 | 2 | 3 | 5 | 7.5 | 10 | 15 | 20 | 25 | 30 | 40 | 50 | 60 | 75 | 100 | 125 | ||
Rating | Type | VFPS1- | ||||||||||||||||
Form | PLE type | 4007PLE | 4015PLE | 4022PLE | 4037PLE | 4055PLE | 4075PLE | 4110PLE | 4150PLE | 4185PLE | 4220PLE | 4300PLE | 4370PLE | 4450PLE | 4550PLE | 4750PLE | 4900PLE | |
PDE type | 4007PDE | 4015PDE | 4022PDE | 4037PDE | 4055PDE | 4075PDE | 4110PDE | 4150PDE | 4185PDE | 4220PDE | 4300PDE | 4370PDE | 4450PDE | 4550PDE | 4750PDE | 4900PDE | ||
Output capacity (kVA) [Note1] | 1.8 | 3.1 | 3.9 | 6.9 | 9.1 | 12 | 17 | 23 | 28 | 33 | 45 | 54 | 65 | 78 | 104 | 124 | ||
Output current (A) [Note2] | 2.3 | 4.1 | 5.1 | 9.1 | 12 | 16 | 22.5 | 30.5 | 37 | 43.5 | 58.5 | 71.5 | 85 | 103 | 137 | 163 | ||
Output voltage | Three-phase 380~480V(The maximum output voltage is equal to the input supply voltage) | |||||||||||||||||
Overload current rating | 110% - 1 minute | |||||||||||||||||
Electrical braking | Dynamic braking circuit | Built-in dynamic braking drive circuit | ||||||||||||||||
Dynamic braking resistor | An external breaking resistor (optional) | |||||||||||||||||
Power supply | Voltage-frequency | Three-phase 380~480V-50/60Hz [Note3] | ||||||||||||||||
Allowable fluctuation | Voltage + 10% - 15% [Note 4] Frequency ±5% | |||||||||||||||||
Protective method | Totally enclosed (JEM1030) IP54 / UL Type 12 [Note 5] | |||||||||||||||||
Cooling method | Forced air-cooled | |||||||||||||||||
Cooling fan noise (dBA) | 43 | 43 | 43 | 55 | 55 | 56 | 56 | 58 | 60 | 60 | 60 | 64 | 64 | 64 | 64 | 64 | ||
Color | RAL7016 | |||||||||||||||||
EMC filter | PLE type | IEC61800-3 category C2(EN55011 class A Group 1) filter Built-in | IEC61800-3 category C3(EN55011 class A Group 2) filter Built-in | |||||||||||||||
PDE type | IEC61800-3 category C1(EN55011 class B Group 1) filter Built-in | |||||||||||||||||
DC reactor | Built-in |
Note 1: Capacity is calculated at 440V.
Note 2: Rated output current when the PWM carrier frequency (parameter CF) is 8kHz or less.
Note 3: An external power supply backup available (optional) (Type: CPS002Z)
Note 4: +/-10% when the inverter is used continuously (load of 100%).
Note 5: Drives with UL Type 12 conformity are optional. Contact your nearest Toshiba inverter distributor for them.